NCT-PKG-002 · round 2 · run e88a0d3965e6

What changed between the revisions

Open the review desk →
6
resolved by the revision
34
still open (incl. unchanged documents)
4
new in the revision
3
documents revised

Unchanged documents keep their findings and the engineer's decisions. Revised documents are read and checked again; every earlier finding is matched to the new result.

NCT-INS-DS-0101

revised · 5 changed passages

Changed passages

sheet 'Datasheet' · row 5 · cell B5
− Revision: A
+ Revision: B
sheet 'Datasheet' · row 7 · cell B7
− Date: 2026-09-14
+ Date: 2026-10-12
sheet 'Datasheet' · row 26 · cell B26
− Calibrated range: 0 - 100 barg
+ Calibrated range: 0 - 250 barg
sheet 'Datasheet' · row 41 · cell B41
− Ingress protection: IP65
− Hazardous area: Ex d IIB T4 Gb, Zone 1
+ Ingress protection: IP66
+ Hazardous area: Ex d IIA T3 Gb, Zone 1
sheet 'Datasheet' · row 50 · cell B50
+ B: 2026-10-12 Updated after owner comments: range, IP rating, hazardous area

Resolved 2

High
NCT-R-INS-001
The calibrated range ends at 100 barg; NCT-INS-SP-0002 Rev 1 §3.1 requires at least 165 barg (1.1 x design pressure).
Medium
NCT-R-INS-002
Ingress protection is IP65, below the minimum IP66 required by NCT-INS-SP-0002 Rev 1 §3.2.

New 1

High
NCT-R-INS-003
'Ex d IIA T3 Gb, Zone 1' is not an allowed value; NCT-INS-SP-0002 Rev 1 §3.3 allows only: gas group IIB or IIC with temperature class T4, T5 or T6.

Still open 2

High
NCT-R-SIS-001
110-PT-1013 is in a safety-instrumented function but only SIL 1 capable; NCT-INS-SP-0011 Rev A §3.1 requires SIL 2.
Medium
NCT-R-INS-009, NCT-R-INS-013
'PT-1012' does not follow the tag format of NCT-INS-SP-0002 Rev 1 §4.1.

NCT-MEC-PR-0701

revised · 8 changed passages

Changed passages

§ Front matter · page header
− North Coast CO2 Trunkline (fictional demo project) NCT-MEC-PR-0701 Rev A
+ North Coast CO2 Trunkline (fictional demo project) NCT-MEC-PR-0701 Rev B
§ Front matter · table row 2 'Revisie'
− Revisie | A
+ Revisie | B
§ Front matter · table row 4 'Datum'
− Datum | 2026-09-25
+ Datum | 2026-10-14
§ 4 Testparameters · table row 3 'Houdtijd'
− Houdtijd | 8 uur
− Testmedium | Gefilterd zoet water (filter 50 micrometer) met corrosie-inhibitor
+ Houdtijd | 24 uur
+ Testmedium | Zeewater, ongefilterd, met corrosie-inhibitor
§ 9 Drogen · heading
− 9 Rapportage en stoppunten
+ 9 Drogen
+ Na het ontwateren wordt de leiding gedroogd met droge lucht tot een waterdauwpunt van -40 degC of lager bij atmosferische druk. Het dauwpunt wordt aan het einde van de sectie gemeten met een gekalibreerde hygrometer en vastgelegd.
+ 10 Rapportage en stoppunten
§ 11 Openstaande punten · heading
− 10 Openstaande punten
+ 11 Openstaande punten
§ 12 Revisiehistorie · heading
− 11 Revisiehistorie
+ 12 Revisiehistorie
§ 12 Revisiehistorie · paragraph 2
+ Rev B, 2026-10-14, houdtijd aangepast, paragraaf drogen toegevoegd, testmedium gewijzigd.

Resolved 2

High
NCT-R-AFP-002
Houdtijd is 8 h, below the minimum of 24 h required by NCT-MEC-SP-0009 Rev A §2.2.
High
NCT-R-AFP-004
No section on this subject was found. Headings present: 1 Doel en toepassingsgebied; 2 Referenties; 3 Veiligheid; 4 Testparameters; 5 Instrumentatie; 6 Uitvoering; 7 Acceptatiecriteria; 8 Ontwateren; 9 Rapportage en stoppunten; 10 Openstaande punten; 11 Revisiehistorie. Required by NCT-MEC-SP-0009 Rev A §3.1.

New 2

High
NCT-R-AFP-003
The document specifies unfiltered seawater as the test medium, which directly contradicts the requirement that the test medium shall be filtered fresh water (50 µm or finer) with a corrosion inhibitor and that seawater is not allowed.
High
NCT-R-PRC-007
The procedure specifies seawater as test medium for a dense-phase CO2 line. Seawater contains dissolved salts and impurities; after drying, residual salt deposits and moisture can remain in the pipe, contradicting the requirement that free water shall never be present in operation and water content shall be max 50 ppmv.

Still open 2

High
NCT-R-AFP-001
Testdruk is 210 barg, below the minimum of 225 barg required by NCT-MEC-SP-0009 Rev A §2.1.
Medium
NCT-R-AFP-006
Kalibratie is 12, above the maximum of 6 allowed by NCT-MEC-SP-0009 Rev A §4.1.

NCT-PRC-PID-0301

revised · 4 changed passages

Changed passages

layer VALVES · block VALVE_BALL #E3
+ VALVE_BALL TAG=110-XV-101 CLASS=CL900
layer NOTES · TEXT at (20, 94) #106
− 1. DESIGN PRESSURE 135 BARG / DESIGN TEMPERATURE -46/+50 DEGC (DISCHARGE AND TRUNKLINE).
+ 1. DESIGN PRESSURE 150 BARG / DESIGN TEMPERATURE -46/+50 DEGC (DISCHARGE AND TRUNKLINE).
layer TITLEBLOCK · title block attribute REV #10D
− Title block REV: A
− Title block DATE: 2026-09-16
+ Title block REV: B
+ Title block DATE: 2026-10-13
layer TITLEBLOCK · title block attribute APPROVED #10D
− Title block APPROVED: (empty)
+ Title block APPROVED: J. DE VRIES

Resolved 2

High
NCT-R-PRC-001, NCT-R-PRC-015
The document states DESIGN PRESSURE = 135 barg; NCT-PRC-DB-0001 Rev D §4.1 requires 150 barg.
Medium
NCT-R-DCC-008
Title block field APPROVED is empty; NCT-DCC-SP-0005 Rev A §2.2 requires it to be filled in.

New 1

Medium
NCT-R-INS-010, NCT-R-INS-009
110-XV-101 appears on this document but not in the instrument index NCT-INS-IL-0501 (NCT-INS-SP-0002 Rev 1 §4.2).

Still open 2

Medium
NCT-R-PRC-020
Line 16"-CO2-1003-B9C is shown on the P&ID but missing from the line list NCT-PIP-LL-0401 (NCT-PRC-DB-0001 Rev D §4.7).
Medium
NCT-R-INS-010
110-PT-1014 appears on this document but not in the instrument index NCT-INS-IL-0501 (NCT-INS-SP-0002 Rev 1 §4.2).

Unchanged documents

findings carried over with status

DocumentOpen findings
NCT-CIV-DW-08013
NCT-INS-IL-05013
NCT-MEC-SP-02016
NCT-PIP-CA-06015
NCT-PIP-LL-04013
NCT-PRC-PID-03023
NCT-QAC-ITP-09015